Tester multifunctional Sonel MPI-536

Solicitati oferta

021 / 314 35 99

Fisiere utile

Broșura Sonel MPI-536

Descriere produs:


Specificatii tehnice

Measurement functions
Measurement range Display range Resolution Accuracy ± (% m.v. + digits)
Fault loop impedance        
Fault loop ZL-PE, ZL-N, ZL-L 0.13 Ω…1999.9 Ω 0.000 Ω…1999.9 Ω from 0.001 Ω ±(5% m.v. + 30 digits)
acc. to IEC 61557
Fault loop ZL-PE in RCD mode from 0.50 Ω…1999 Ω 0.00 Ω…1999 Ω from 0.01 Ω from ±(6% m.v. + 5 digits)
acc. to IEC 61557
Measurements of RCD parameters        
RCD tripping test and measurement of tripping time tA
measuring current 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
general and short-time delay RCD 0 ms…300 ms 0 ms…300 ms 1 ms from ±(2% m.v. + 2 digits)
selective RCD 0 ms…500 ms 0 ms…500 ms 1 ms from ±(2% m.v. + 2 digits)
Measurement of RCD tripping current IA        
measuring current 0.2 IΔn…2.0 IΔn
for sinusoidal residual current (AC type) 3.3 mA…1000 mA 3.3 mA…1000 mA from 0.1 mA ±5% IΔn
for unidirectional residual current and 3.5 mA…700 mA 3.5 mA…700 mA from 0.1 mA ±10% IΔn
unidirectional with the 6 mA DC bias (type A)
for direct residual current (type B) 2.0 mA…1000 mA 2.0 mA…1000 mA from 0.1 mA ±10% IΔn
Earth resistance        
3- and 4-pole method from 0.50 Ω…1.99 kΩ 0.00 Ω…1.99 kΩ from 0.01 Ω from ±(2% m.v. + 3 digits)
acc. to IEC 61557-5
3-pole + clamp method 0.00 Ω…1.99 kΩ 0.00 Ω…1.99 kΩ from 0.01 Ω from ±(2% m.v. + 4 digits)
2-clamp method 0.00 Ω…99.9 kΩ 0.00 Ω…99.9 kΩ from 0.01 Ω from ±(10% m.v. + 4 digits)
Resistance-to-earth 0.0 Ωm…99.9 kΩm 0.0 Ωm…99.9 kΩm from 0.1 Ωm Depending on accuracy
of RE measurement
Insulation resistance        
Measuring voltage 10 V 10 kΩ…9.99 MΩ 0 kΩ…9.99 MΩ from 1 kΩ from ±(3% m.v. + 8 digits)
acc. to IEC 61557-2
Measuring voltage 50 V 50 kΩ…250 MΩ 0 kΩ…250 MΩ from 1 kΩ from ±(3% m.v. + 8 digits)
acc. to IEC 61557-2
Measuring voltage 100 V 100 kΩ…500 MΩ 0 kΩ…500 MΩ from 1 kΩ from ±(3% m.v. + 8 digits)
acc. to IEC 61557-2
Measuring voltage 250 V 250 kΩ…999 MΩ 0 kΩ…999 MΩ from 1 kΩ from ±(3% m.v. + 8 digits)
acc. to IEC 61557-2
Measuring voltage 500 V 500 kΩ…2.00 GΩ 0 kΩ…2.00 GΩ from 1 kΩ from ±(3% m.v. + 8 digits)
acc. to IEC 61557-2
Measuring voltage 1000 V 1000 kΩ…3.00 GΩ 0 kΩ…3.00 GΩ from 1 kΩ from ±(3% m.v. + 8 digits)
acc. to IEC 61557-2
Measuring voltage 1500 V 1500 kΩ…5.00 GΩ 0 kΩ…5.00 GΩ from 1 kΩ from ±(3% m.v. + 8 digits)
acc. to IEC 61557-2
Measuring voltage 2500 V 2500 kΩ…9.99 GΩ 0 kΩ…9.99 GΩ from 1 kΩ from ±(3% m.v. + 8 digits)
acc. to IEC 61557-2
Resistance of protective conductors and equipotential bondings
Measurement of resistance of protective conductors and equipotential bondings 0.12 Ω…400 Ω      
with ±200 mA current acc. to IEC 61557-4 0.00 Ω…400 Ω from 0.01 Ω ±(2% m.v. + 3 digits)
Measurement of resistance with low current 0.0 Ω…1999 Ω 0.0 Ω…1999 Ω from 0.1 Ω ±(3% m.v. + 3 digits)
Light intensity        
Measurement in luxes (lx) 0 lx…399.9 klx 0 lx…399.9 klx from 0.001 lx from ±(2% m.v. + 5 digits)
Measurement in feet-candles (fc) 0 fc…39.99 kfc 0 fc…39.99 kfc from 0.001 fc from ±(2% m.v. + 5 digits)
Phase sequence indication in the same direction (correct), opposite direction (incorrect), UL-L voltage: 95 V…500 V (45 Hz…65 Hz)